PHYSICAL PROPERTIES |
|
PROPERTY |
RESULT |
Color |
Red |
Thickness |
0.75mm (30 mil) |
Membrane Weight |
249.6 g/m² (0.818oz/ft²) |
Roll Weight (with release film) |
25.9 kg (57.2 lbs) |
Roll Dimensions |
1.5m x 31m (59" x 164') |
Roll Coverage |
75m² (807 ft²) |
Skid |
16 rolls |
Primer |
No Primer Required |
VOCs |
None |
Field Exposure Before Permanent Cladding |
6 months, 180 days |
Minimum Application Temperature |
-6.6°C (20° F) and rising |
Service Temperature |
-40°C (40°F) 121°C (250°F) |
Warranty |
20 year material warranty |
TESTING DATA |
||
PROPERTY |
STANDARD |
RESULT |
Strength |
||
Dry Tensile Strength ≥ 20 lbf/in |
ASTM D828 Standard Test Method for Tensile Properties of Paper and Paperboard Using Constant-Rate-of-Elongation Apparatus |
6.1 N/mm(34.8 lbf) |
Dry Breaking Force (Grab method) MD ≥40 XMD ≥35 |
ASTM D5034 Standard Test Method for Breaking Strength and Elongation of Textile Fabrics (Grab Test) |
MD - 391 N (88 lbf) XMD - 369 N (83 lbf) |
Cold Mandrel Bend Test |
AC38 Section 3.3.4 |
Warp (Machine) Direction - No cracking Filling (Cross) Direction - No cracking |
Weathering Tests |
AC38 Section 4.1.2 UV Exposure AC38 Section 4.1.3 Accelerated Aging |
UV - No visual change UV & Accelerated - visibly lighter, no visible deterioration |
Water Vapor Transmittance |
||
Water Vapor Transmission Desiccant Method, Procedure A, 24.4°C (76.0°F) 50 %RH |
ASTM E96 Standard Test Methods for Water Vapour Transmission of Materials |
8.5 Perm (grain/h•ft2•inchHg) 486 ng/Pa•s•m2 |
Water Vapour Transmission Water Method, Procedure B, 24.4°C (76.0°F) 50 %RH |
ASTM E96 Standard Test Methods for Water Vapour Transmission of Materials |
24 Perm (grains/hr•ft2•inchHg) 1373 ng/Pa•s•m2 |
Water Vapour Transmission Dynamic Relative Humidity Measurement (23°C 50 %RH) |
ASTM E398 Standard Test Method for Water Vapour Transmission Rate of Sheet Materials Using Dynamic Relative Humidity Measurement |
20.47 Perm (grain/h•ft2•inchHg) |
Air Resistance Testing |
||
Air Permeance |
ASTM E2178 @75 Pa Standard Test Method for Air Permeance of Building Materials |
0.0014 L/s m² @ 75 Pa (0.000276 cfm/ft² @ 1.57 psf ) |
Air Barrier | ASTM E2357 Standard Test Method for Determining Air Leakage of Air Barrier Assemblies | 0.0194 L/(s·m²) at 75 Pa (0.0039 cfm/ft² @ 1.57 psf) |
Air Permeance | CAN/ULC-S741-08 (2020) Standard for Air Barrier Materials | PASS |
Air Leakage Rate | CAN/ULC-S742-11 Standard for Air Barrier Assemblies | Class A1 |
Adhesion Testing |
||
Peel Adhesion |
AAMA 711 |
PASS |
Water Resistance Testing |
||
Nail Sealability |
ASTM D1970/ section 7.9 Standard Specification for Self-Adhering Polymer Modified Bituminous Sheet Materials Used as Steep Roofing Underlayment for Ice Dam Protection |
|
Water Resistance (Boat Test) |
ASTM D779 Standard Test Method for Water Resistance of Paper, Paperboard, and Other Sheet Materials by the Dry Indicator Method (Withdrawn 2011) |
Control - No leakage |
Water Resistance (Control after Weathering) |
AATCC 127 Hydrostatic pressure test (550 mm water column for 5 hours), American Association of Textile Chemists and Colourists |
Control - No leakage |
Fire Testing |
||
Flame Spread Smoke Developed |
ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials |
Flame Spread 10 Smoke Developed 10 |
Surface Burning Characteristics | CAN/ULC-S102 Protective underlayment, Permeable to allow drying, Provides an Air Barrier | Flame Spread Rating: 5 Smoke Developed Value: 20 |